The indoor sounders are used independently for signaling an alarm directly at the fire location.
Functions
The device allows to select 32 types of alarm and evacuation tones (including DIN tone 33404, part 3) for different requirements.
You can adjust the sound pressure by five levels according to the operational environment. Depending on the tone type and volume set, the sound pressure varies between 65 dB(A) and 101dB(A).
Sounders of the same LSN loop and with the same tone type provide immediate synchronization. The device maintains LSN loop functions in the event of wire interruption or short-circuit thanks to two integrated isolators.
Change of the device settings can be done in the FSP-5000-RPS programming software.
Certifications and approvals
Complies with
Installation/configuration notes
2 | FNM-420-A Sounder Indoor
Sound pressure level specified with a tolerance of ±3 dB(A), measured at a distance of 1 m. Constant sound pressure level between 22 V and 33 V operating voltage.
Default setting: tone in line with DIN 33404, part 3
Results from EN54-3 testing: lowest value at 15 V at maximum volume level, measured on the measurement axis with the highest results. All other measurements are taken 'on axis' and are not third party verified.